Heat Shirnkable Terminations suitable for 3 core XLPE/EPR/PVC Insulated Cable upto 36KV
GXO/I- 1936
Descriptions:
GXO/I - 1936 - Series termination kits are heat shrinkable type, designed for 3 core extruded dielectric, shielded, armoured/unarmoured XLPE/EPR/PVC Insulated cables upto 36 KV rated voltage (19/33KV, Um=36KV). Our kits has been designed to provide the basic important functions required for medium voltage power cable accessories including the electrical performance, stress relief measures, environmental seal, mechanical fatigues & other related performance parameters laid down in different countries for various service conditions. These are designed, manufactured and tested according to requirements of the local & internationally accepted standards.
Salient Features:
- Fits a wide dimensional range.
- Excellent electrical, thermal & mechanical performance.
- Accommodation of tolerances, different conductor cross sections & cable constructions.
- No shelf life limitations upto or below 50 deg C.
- Pre-designed components for easy & reliable installation.
- Each kit contains easy to follow instructions with well explained visual & graphics for step wise installation methods.
- Exceptional Insulation properties.
- High tracking resistance in harsh environment.
Specifications:
Test Sequence | Requirement Test Value | Results |
---|---|---|
A.C. Voltage Withstand, 5 Min | 85.5 Kv, no Flashover | Pass |
D.C. Voltage Withstand, 15 Min | 76 kV, no Flashover | pass |
Partial Discharge | 36 kV < 10Pc Max. | > 36 kV |
Impulse Withstand Voltage | 170 kV, no Flashover | No Problem |
Order Reference:
Cable Range (Sq. mm) | Indoor Kit Code | Outdoor kit Code |
---|---|---|
16-50 | GXI-31 | GXO-31 |
70-95 | GXI-32 | GXO-32 |
120-185 | GXI-33 | GXO-33 |
240-300 | GXI-34 | GXO-34 |
400-500 | GXI-35 | GXO-35 |
© 2021 Ele Chem Systems Pvt.Ltd.. All Right Reserved